Product Details
The Fireye ZB230UVSC is a microprocessor-based BurnerLogix Z-series integrated burner management chassis with built-in UV self-check flame amplifier, rated for 230 VAC supply. This BurnerLogix burner management chassis combines standard burner sequencing safety logic and PID boiler modulation control, supporting automatic ignition, pre-purge, trial for ignition, flame supervision and safe shutdown for gas, light oil and dual-fuel burners. As a reliable UV self-check flame amplifier, it performs automatic internal diagnostic checks on the UV flame scanner during each firing cycle to detect sensor faults and reduce unsafe false operation. This Fireye boiler combustion controller is stocked as genuine replacement spare part, widely used to retrofit and maintain automatic boilers, process heaters and packaged combustion systems.
Basic Parameters
Brand: Fireye
Model: ZB230UVSC
Type: BurnerLogix Z-series chassis with UV self-check amplifier
Supply voltage: 230 VAC, 50 / 60 Hz
Power consumption: 25 VA
Flame input: UV self-check scanner compatible
Optional modules: Plug-in programmer module, BLV512 VFD display, BLL510 LCD display
Supported fuels: Natural gas, propane, light fuel oil, combination fuel
Control function: Burner sequencing, flame safeguard, PID temperature / pressure modulation
Approval: FM, CE certified
Product type: Original Fireye burner management spare chassis
Supported Functions
This BurnerLogix burner management chassis executes the complete safe burner startup sequence including pre-purge, ignition trial and run-time flame monitoring. The UV self-check flame amplifier continuously verifies scanner health while monitoring flame presence; it triggers immediate lockout and fuel shutoff upon flame loss or scanner failure. This Fireye boiler combustion controller supports local setpoint adjustment, lead-lag boiler operation, password protection and remote communication for status reading and parameter modification.
Core Functions
The self-check UV amplifier validates scanner integrity every cycle to eliminate hidden sensor failures that could bypass flame protection. The BurnerLogix burner management chassis coordinates blower, ignition transformer and fuel valve outputs following certified safety timing. Built-in PID control maintains stable boiler output by modulating firing rate against pressure or temperature setpoints. Modular design allows direct swap for a faulty ZB230UVSC chassis, with compatible plug-in programmers and displays for quick commissioning.
Hardware Specifications & Environmental Features
Mounting: DIN rail or panel chassis installation
Operating temperature: -40 °C to +60 °C
Storage temperature: -40 °C to +70 °C
Relative humidity: 5% – 90%, non-condensing
Enclosure rating: NEMA 1
Condition: Original new or fully tested refurbished Fireye spare part
Industry Applications: Applied in legacy petrochemical distributed control, old paper making production automation, material handling conveyor lines, packaging and textile machinery, water treatment remote signal collection and large conveyor remote I/O control racks.
Note: Confirm 800 series backplane compatibility, pulse signal type, counting mode and preset logic before ordering.