Product Details
The Fireye R9006M3011 is a panel‑mounted flame supervision amplifier belonging to the Fireye R9000 series, designed exclusively for non self‑checking C9506 flame scanners. This panel mounted flame controller captures weak optical flame signals from the C9506 probe, amplifies and filters the waveform, and provides fail‑safe relay output for burner safety interlock. As a reliable C9506 non self-check scanner amplifier, it is powered by 220 VAC, equipped with front analog flame meter, flame-on LED and fault indicator, plus adjustable gain and threshold to reduce false flame signals from hot refractory and stray light. This 220VAC flame supervision unit is widely used on industrial boilers, furnaces and process heaters burning natural gas and fuel oil and stocked as genuine replacement spare part for legacy Fireye combustion safety systems.
Basic Parameters
Brand: Fireye
Model: R9006M3011
Type: Panel‑mount flame amplifier / flame controller
Supply voltage: 220 VAC, 50 / 60 Hz
Compatible scanner: Non self-check C9506 series flame scanners
Supported fuels: Natural gas, light fuel oil
Indication: Analog flame strength meter, flame LED, fault status indicator
Adjustment: Signal gain, flame detection threshold
Variant note: R9006M3000 is the 120 VAC counterpart
Certifications: UL, CE listed
Product type: Original Fireye flame supervision control module
Supported Functions
This controller continuously monitors optical radiation received from the C9506 scanner. When stable flame radiation is detected, it maintains the safety relay closed to permit burner continuous firing. If flame disappears during operation or no valid flame is proven after ignition trial, it de‑energizes the safety relay, triggers lockout and cuts fuel supply. Since it works with non self‑check scanners, regular burner cycling is required to verify scanner integrity.
Core Functions
The standard panel cutout mounting allows installation on cabinet doors for convenient visual access. The front analog meter lets service technicians read real‑time flame intensity during commissioning and routine inspection. Tunable gain and threshold adapt the unit for different sight distances and flame brightness levels. It serves as direct drop‑in substitution for existing R9006M3011 flame controllers.
Hardware Specifications & Environmental Features
Mounting: Panel cutout installation
Operating temperature: -40 °C to +79 °C
Storage temperature: -40 °C to +70 °C
Relative humidity: 5% – 90%, non‑condensing
Housing: Rugged metal front panel assembly
Condition: New surplus or fully tested refurbished Fireye spare part
Industry Applications: Applied in legacy petrochemical distributed control, old paper making production automation, material handling conveyor lines, packaging and textile machinery, water treatment remote signal collection and large conveyor remote I/O control racks.
Note: Confirm non self-check C9506 scanner matching and 220V power supply before ordering; this unit cannot pair with self-check scanners or other scanner families such as C9508.
This is from our current stock.